An industrial heat pump captures heat at low temperature, often waste heat, and delivers it at a level useful to the process. It advantageously replaces a fossil boiler when the temperature lift to bridge stays moderate.

Updated on

What determines performance

  • Temperature lift between source and use: the smaller it is, the higher the coefficient of performance (COP).
  • Typical COP: around 3 to 5 for lifts of 40 to 60 K, roughly half the theoretical Carnot COP.
  • Price ratio between electricity and gas, which decides profitability as much as technology.
  • Output temperature: commercial offers commonly reach 120 to 150 °C; beyond that, solutions are at demonstration stage.

Choice of fluid and source

Ammonia, hydrocarbons, CO₂ and new-generation HFO-type fluids share the market; the F-gas Regulation (EU) 2024/573 progressively phases down high-warming-potential fluids. Typical sources are cooling water, condensates, compressed air, process discharges between 30 and 80 °C or treated effluents.

Integration in the site

A typical project compares the levelised cost of heat produced with the existing solution, includes the carbon price and available aid, then tests sensitivity to energy prices. Production stops, exchanger fouling and compressor maintenance must be included in the file.

Tracking indicators

Track real COP over the year, not just at nominal point, the share of heat covered, operating hours and availability. These indicators feed the site’s energy management plan and justify any capacity extension.

Key takeaway: the best heat pump project starts with the best heat-recovery project. Reduce demand, match source and sink temperatures carefully, and design controls that keep the COP high throughout the year.